Information identified as archived on the Web is for reference, research or recordkeeping purposes. It has not been altered or updated after the date of archiving. Web pages that are archived on the Web are not subject to the Government of Canada Web Standards. As per the Communications Policy of the Government of Canada, you can request alternate formats. Please "contact us" to request a format other than those available.

Download Full Document (PDF, 850 kb document)

CETC Number 2011-189 / 2012-03-13

Michael Wrinch, Hedgehog Technologies
Tarek EL-Fouly and Steven Wong, CanmetENERGY

Abstract

This paper presents and demonstrates a method to quickly identify when regular periodic activities, such as a daily night setback on a thermostat, are inappropriately configured or accidentally reset. Anomalies in periodic building operations are identified by analyzing smart meter electrical demand data in the frequency domain with a weekly travelling time window instead of using time domain functions such as load factor. Initial experiments on a real site found that spectral energy signals for periodic (frequency) hours of 4, 6, 8, 12 and days 1, 3.5 and 7 to be greatly reduced when a device is not functioning appropriately. In addition, the ratio of the DC offset (0 Hz) energy with the other higher periodic energies can normalize the periodic energies to a relative index that can then be used for comparing other seasons and other buildings for periodical performance.

Page details

Report a problem on this page
Please select all that apply:

Thank you for your help!

You will not receive a reply. For enquiries, contact us.

Date modified: